Mounting Instructions for IP65 Drivers The IP65 driver is designed for outdoor applications in open air. If it is used indoors it is important to ensure adequate airflow around the driver so that the localised ambient does not significantly increase. The diagram below gives guidance for the minimum distance from walls and ceiling. If grouping drivers, the installer must ensure spacing between each driver horizontally of at least 200mm and vertically 300mm. Importantly the spacing information provided here is only a guide and it is the installers responsibility to check that the localised ambient does not exceed the “ta” rating in these specifications. In both outdoor and indoor applications the IP65 drivers must be mounted vertically with the cable entries at the bottom. Suitable IP rated cable glands or conduit glands must be used to maintain the driver IP rating. Refer to drawing below for “tc” location. Use the sleeving supplied with the driver to over sleeve individual low temperature cables from entry gland to the terminal block.
Solid Roof
300mm
(minimum)
UP
CL
200mm (minimum)
70
CABLES
Tc 65°C
IMPORTANT! Not user repairable. Do not remove covers as warranty may be voided. Only loosen M8 latch bolt on main enclosure lid to access terminals.
CABLES. Refer to installation instructions for detail on oversleeving cables.