Schreder OWLET IV NEMA Installation Instructions

SELF-TEST PREPARATION 11 1

SELF-TEST PHASE 1

Note : The self-test occurs only in the first 5 power cycles after installing the controller. * 1-10V can take longer than 10 seconds between cycles.

2

The controller reduces light to 0%.

The controller increases light to 100%.

The controller reduces light to driver minimum value.

The controller switches OFF the light completely.

When powering on the luminaire, the light switches ON to maximum level.

0%

0%

100%

Driver minimum

100%

10 seconds

10 seconds

10 seconds

10 seconds

PHASE 2 DAY-TIME SELF-TEST

FAIL - Luminaire is OFF . Light does not turn on. RED light in the controller is ON .

3

4

OPTIONAL MOTION DECTECTION TEST Trigger a motion detection in the luminaire during day-time test.

PASS - Luminaire is ON . Light decreases from 100% to 20%.

FAIL - Light level does not change.

PASS - Light level increases to 100% then decreases to initial level.

100% 20%

0%

20% 100% 20%

20%

20%

120 minutes

NIGHT-TIME SELF-TEST

5

6

OPTIONAL MOTION DECTECTION TEST Trigger a motion detection in the luminaire during night- time test.

PASS - Luminaire is ON . Light decreases from 100% to 20% then increases to 100%.

FAIL - Luminaire is ON. Light is at 100%. RED light in the controller is ON .

PASS - Light level decreases from 100% to 70% then increases to initial level.

FAIL - Light level does not change.

100%

100% 20%

100%

100% 100%

100%

70%

100%

120 minutes

7

After the self-test, the luminaire operates as configured on the Schréder EXEDRA platform.

www.schreder.com /4

4

DOC-0020638 OWLET IV NEMA-INS-D | 03-2025