SELF-TEST PREPARATION 11 1
SELF-TEST PHASE 1
Note : The self-test occurs only in the first 5 power cycles after installing the controller. * 1-10V can take longer than 10 seconds between cycles.
2
The controller reduces light to 0%.
The controller increases light to 100%.
The controller reduces light to driver minimum value.
The controller switches OFF the light completely.
When powering on the luminaire, the light switches ON to maximum level.
0%
0%
100%
Driver minimum
100%
10 seconds
10 seconds
10 seconds
10 seconds
PHASE 2 DAY-TIME SELF-TEST
FAIL - Luminaire is OFF . Light does not turn on. RED light in the controller is ON .
3
4
OPTIONAL MOTION DECTECTION TEST Trigger a motion detection in the luminaire during day-time test.
PASS - Luminaire is ON . Light decreases from 100% to 20%.
FAIL - Light level does not change.
PASS - Light level increases to 100% then decreases to initial level.
100% 20%
0%
20% 100% 20%
20%
20%
120 minutes
NIGHT-TIME SELF-TEST
5
6
OPTIONAL MOTION DECTECTION TEST Trigger a motion detection in the luminaire during night- time test.
PASS - Luminaire is ON . Light decreases from 100% to 20% then increases to 100%.
FAIL - Luminaire is ON. Light is at 100%. RED light in the controller is ON .
PASS - Light level decreases from 100% to 70% then increases to initial level.
FAIL - Light level does not change.
100%
100% 20%
100%
100% 100%
100%
70%
100%
120 minutes
7
After the self-test, the luminaire operates as configured on the Schréder EXEDRA platform.
www.schreder.com /4
4
DOC-0020638 OWLET IV NEMA-INS-D | 03-2025